Portable three phase power logger designed for energy monitoring and load studies. Large graphical display for instant viewing of results and easy on-screen setup. Ships complete with switchable-range 3000A flexible current transformers and software.
Portable three phase power logger designed for energy monitoring and load studies. Large graphical display for instant viewing of results and easy on-screen setup. Ships complete with switchable-range 3000A flexible current transformers and software.
Discontinued!
This product has been discontinued and is no longer available.
This is the direct replacement:
Features:
Display | ¼ VGA Graphic Color transmissive displays 320 x 240 Pixel with additional background lighting and adjustable contrast, text and graphics in color |
Quality | Developed, designed and manufactured according to DIN ISO 9001 |
Memory | 4 MB Flash memory, 3.5 MB for measuring data |
Interface | RS-232 SUB-D socket; 115.2 k Baud, 8 data bits, no parity, 1 stop bit, firmware updates are possible with the RS- 232 interface (9-pole extension cable) |
Sample rate | 10.24 kHz |
Line frequency | 50 Hz or 60 Hz, user-selectable, with automatic synchronization |
Power supply | NiMH battery-pack, with ac adapter (15 V to 20 V/0.8 A) |
Operation time with battery | Typical > 12 hours without backlight and > 6 hours with backlight high |
Dimensions | 240 mm x 180 mm x 110 mm |
Weight | 1.7 kg, including battery |
Working temperature range | -10 °C to +50 °C |
Storage temperature range | -20 °C to +60 °C |
Operating temperature range | 0 °C to +40 °C |
Reference temperature range | 23 °C ± 2 °C |
Note | The above terms are defined in European Standards. To calculate the specification at any point in the working temperature range, use the temperature coefficient below. |
Temperature coefficient | ± 0.1 % of the measured value per °C from the reference |
Intrinsic error | Refers to reference temperature, maximum deviation is guaranteed for two years |
Operating error | Refers to operating temperature range, maximum deviation is guaranteed for two years |
Climatic class | C1 (IEC 654-1) -5 °C to +45 °C, 5% to 95% RH, no dew |
Housing | Cycoloy shock and scratch proof thermoplast V0-type (non-flammable) with rubber protection holster |
Emission | IEC/EN 61326-1:1997 class B |
Immunity | IEC/EN 61326-1:1997 |
Safety | IEC 61010-1 600 V CAT III, double or reinforced insulation, pollution degree 2 |
Protection | IP65; EN60529 (refers only to the main housing without the battery compartment) |
RMS values are measured with a 20 ms resolution. |
Measuring range | 57 V/66 V/110 V/120 V/127 V/220 V/230 V/240 V/260 V/277 V/347 V/380 V/400 V/417 V/480 V ac |
Intrinsic error | ± (0.2% of measured value + 5 digits) |
Operating error | ± (0.5% of m. v. + 10 digit) |
Resolution | 0.1 V |
Measuring range | 100 V/115 V/190 V/208 V/220 V/380 V/400 V/415 V/450 V/480 V/600 V/660 V/690 V/720 V/830 V ac |
Intrinsic error | ± (0.2% of m. v. + 5 digit) |
Operating error | ± (0.5 % of m. v. + 10 digit) |
Resolution | 0.1 V |
Flexi set I ranges | 15 A/150 A/3000 A rms (at sine) |
Current clamp ranges | 1 A/10 A |
Resolution | 0.01 A |
Ranges | 150 A/3000 A and 1 A/10 A |
Intrinsic error | ± (0.5 % of m. v. + 10 digit) |
Operating error | ± (1 % of m. v. + 10 digit) |
Ranges | 15 A |
Intrinsic error | ± (0.5 % of m. v. + 20 digit) |
Operating error | ± (1 % of m. v. + 20 digit) |
The errors of the current probes are not considered. |
Flexi Set measuring error | ± (2% of m. v. + 10 digit) |
Position influence | ± (3 % of m. v. + 10 digit) |
CF (typical) | 2.83 |
Note | When using Flexi Set please make sure to position the conductor opposite to the Flexi Set-lock |
Measuring range | see V rms and A rms measurement |
Power errors are calculated by adding the errors of voltage and current | |
Additional error due to power factor PF | |
Specified error x (1-[PF]) | |
Maximum range with voltage range 830 V delta-connection and 3000 A current range is 2.490 MW, higher displayed values possible when using PTs and CTs with ratio feature | |
Intrinsic error | ± (0.7 % of m.v. +15 digit) |
Resolution | 1 kW |
Operating error | ± (1.5 % of m.v. + 20 digit) |
Typical range with voltage range 230 V wye connection and 150 A current range is 34.50 KW. | |
Intrinsic error | ± (0.7 % of m.v. +15 digit) |
Resolution | 1 W to 10 W |
Operating error | ± (1.5 % of m.v. + 20 digit) |
The errors of the current sensors themselves have not been considered. |
Intrinsic error | ± (0.7 % of m.v.+ F variation error* + 15 digit) |
Resolution | 1 W to 10 W |
Operating error | ± (1.5 % of m.v. + F variation error* + 20 digit) |
*Frequency variation error |
Range | 0.000 to 1.000 |
Resolution | 0.001 |
Accuracy | ±1 % of full scale |
Measuring range | 46 Hz to 54 Hz and 56 Hz to 64 Hz |
Intrinsic error | ± (0.2 % of m. v. + 5 digit) |
Operating error | ± (0.5 % of m. v.+ 10 digit) |
Resolution | 0.01 Hz |
Measuring range | To 50th harmonic (< 50 % of nom) |
Vm, Im, THDV, THDI | IEC 61000-4-7:2002, Class II |
Vm > 3% Vn | ± 5% Vm |
Vm < 3 % Vnom | ±0.15% Vnom |
Im > 10 % Inom | ± 5% Im |
Im < 10 % Inom | ± 0 5% Inom |
THDV | for THD < 3% ± 0.15% at Vnom for THD > 3% ± 5% at Vnom |
THDI | for THD < 10% ± 0.5% at Inom for THD > 10% ± 5% at Inom |
Vnom | Normal voltage range |
Inom | Nominal current range |
Vm and Im are measured values of harmonic m |
Detection of voltage dips, voltage swells and voltage interruptions with a 10 ms resolution and measuring error of the half period sine wave of rms. | |
Intrinsic error | ± (1% of m.v. + 10 digit) |
Operating error | ± (2% of m.v. + 10 digit) |
Resolution | 0.1 V |
Click on a category to view a selection of compatible accessories with the Fluke 1735 Portable Power Logger.
Display | ¼ VGA Graphic Color transmissive displays 320 x 240 Pixel with additional background lighting and adjustable contrast, text and graphics in color |
Quality | Developed, designed and manufactured according to DIN ISO 9001 |
Memory | 4 MB Flash memory, 3.5 MB for measuring data |
Interface | RS-232 SUB-D socket; 115.2 k Baud, 8 data bits, no parity, 1 stop bit, firmware updates are possible with the RS- 232 interface (9-pole extension cable) |
Sample rate | 10.24 kHz |
Line frequency | 50 Hz or 60 Hz, user-selectable, with automatic synchronization |
Power supply | NiMH battery-pack, with ac adapter (15 V to 20 V/0.8 A) |
Operation time with battery | Typical > 12 hours without backlight and > 6 hours with backlight high |
Dimensions | 240 mm x 180 mm x 110 mm |
Weight | 1.7 kg, including battery |
Working temperature range | -10 °C to +50 °C |
Storage temperature range | -20 °C to +60 °C |
Operating temperature range | 0 °C to +40 °C |
Reference temperature range | 23 °C ± 2 °C |
Note | The above terms are defined in European Standards. To calculate the specification at any point in the working temperature range, use the temperature coefficient below. |
Temperature coefficient | ± 0.1 % of the measured value per °C from the reference |
Intrinsic error | Refers to reference temperature, maximum deviation is guaranteed for two years |
Operating error | Refers to operating temperature range, maximum deviation is guaranteed for two years |
Climatic class | C1 (IEC 654-1) -5 °C to +45 °C, 5% to 95% RH, no dew |
Housing | Cycoloy shock and scratch proof thermoplast V0-type (non-flammable) with rubber protection holster |
Emission | IEC/EN 61326-1:1997 class B |
Immunity | IEC/EN 61326-1:1997 |
Safety | IEC 61010-1 600 V CAT III, double or reinforced insulation, pollution degree 2 |
Protection | IP65; EN60529 (refers only to the main housing without the battery compartment) |
RMS values are measured with a 20 ms resolution. |
Measuring range | 57 V/66 V/110 V/120 V/127 V/220 V/230 V/240 V/260 V/277 V/347 V/380 V/400 V/417 V/480 V ac |
Intrinsic error | ± (0.2% of measured value + 5 digits) |
Operating error | ± (0.5% of m. v. + 10 digit) |
Resolution | 0.1 V |
Measuring range | 100 V/115 V/190 V/208 V/220 V/380 V/400 V/415 V/450 V/480 V/600 V/660 V/690 V/720 V/830 V ac |
Intrinsic error | ± (0.2% of m. v. + 5 digit) |
Operating error | ± (0.5 % of m. v. + 10 digit) |
Resolution | 0.1 V |
Flexi set I ranges | 15 A/150 A/3000 A rms (at sine) |
Current clamp ranges | 1 A/10 A |
Resolution | 0.01 A |
Ranges | 150 A/3000 A and 1 A/10 A |
Intrinsic error | ± (0.5 % of m. v. + 10 digit) |
Operating error | ± (1 % of m. v. + 10 digit) |
Ranges | 15 A |
Intrinsic error | ± (0.5 % of m. v. + 20 digit) |
Operating error | ± (1 % of m. v. + 20 digit) |
The errors of the current probes are not considered. |
Flexi Set measuring error | ± (2% of m. v. + 10 digit) |
Position influence | ± (3 % of m. v. + 10 digit) |
CF (typical) | 2.83 |
Note | When using Flexi Set please make sure to position the conductor opposite to the Flexi Set-lock |
Measuring range | see V rms and A rms measurement |
Power errors are calculated by adding the errors of voltage and current | |
Additional error due to power factor PF | |
Specified error x (1-[PF]) | |
Maximum range with voltage range 830 V delta-connection and 3000 A current range is 2.490 MW, higher displayed values possible when using PTs and CTs with ratio feature | |
Intrinsic error | ± (0.7 % of m.v. +15 digit) |
Resolution | 1 kW |
Operating error | ± (1.5 % of m.v. + 20 digit) |
Typical range with voltage range 230 V wye connection and 150 A current range is 34.50 KW. | |
Intrinsic error | ± (0.7 % of m.v. +15 digit) |
Resolution | 1 W to 10 W |
Operating error | ± (1.5 % of m.v. + 20 digit) |
The errors of the current sensors themselves have not been considered. |
Intrinsic error | ± (0.7 % of m.v.+ F variation error* + 15 digit) |
Resolution | 1 W to 10 W |
Operating error | ± (1.5 % of m.v. + F variation error* + 20 digit) |
*Frequency variation error |
Range | 0.000 to 1.000 |
Resolution | 0.001 |
Accuracy | ±1 % of full scale |
Measuring range | 46 Hz to 54 Hz and 56 Hz to 64 Hz |
Intrinsic error | ± (0.2 % of m. v. + 5 digit) |
Operating error | ± (0.5 % of m. v.+ 10 digit) |
Resolution | 0.01 Hz |
Measuring range | To 50th harmonic (< 50 % of nom) |
Vm, Im, THDV, THDI | IEC 61000-4-7:2002, Class II |
Vm > 3% Vn | ± 5% Vm |
Vm < 3 % Vnom | ±0.15% Vnom |
Im > 10 % Inom | ± 5% Im |
Im < 10 % Inom | ± 0 5% Inom |
THDV | for THD < 3% ± 0.15% at Vnom for THD > 3% ± 5% at Vnom |
THDI | for THD < 10% ± 0.5% at Inom for THD > 10% ± 5% at Inom |
Vnom | Normal voltage range |
Inom | Nominal current range |
Vm and Im are measured values of harmonic m |
Detection of voltage dips, voltage swells and voltage interruptions with a 10 ms resolution and measuring error of the half period sine wave of rms. | |
Intrinsic error | ± (1% of m.v. + 10 digit) |
Operating error | ± (2% of m.v. + 10 digit) |
Resolution | 0.1 V |
Click on a category to view a selection of compatible accessories with the Fluke 1735 Portable Power Logger.