Whether you work with utility-scale solar PV arrays, wind power, electric railways, or data centers, this digital multimeter is ideal for technicians working in any DC environment up to 1500 V. In addition, this enhances your safety and increases productivity while giving you accurate, reliable, and repeatable results.
Whether you work with utility-scale solar PV arrays, wind power, electric railways, or data centers, this digital multimeter is ideal for technicians working in any DC environment up to 1500 V. In addition, this enhances your safety and increases productivity while giving you accurate, reliable, and repeatable results.
The 283 FC includes TL175-HV CAT III 1500 V/CAT IV 1000 V safety-rated silicone TwistGuard test leads for working in higher voltage environments without compromising safety, giving you more flexibility when testing voltage, millivoltage, resistance, continuity, or capacitance. The backlit LCD screen and illuminated keypad make it easier to work in various lighting conditions while the magnetic hanging kit frees up your hands while testing. The 283 FC also includes a custom hard carrying case that protects your investment while you transport it.
Features
User-Defined Limit Gauge
On large-scale PV projects where you’re taking repetitive measurements and expect consistent results, the user-defined limit gauge becomes a vital time-saving tool. The adjustable limit gauge can trigger audio and visual indications whenever a measurement falls outside your expected range. This saves you time letting you quickly evaluate measurement results, increasing your confidence in the system's performance, and helping to identify potential issues that need to be addressed.
With the dedicated limit gauge button, you can easily turn the limit gauge warnings on and off, set up new measurement parameters, or select from previously used parameter profiles. This customization streamlines troubleshooting, allowing you to quickly identify measurement deviations or errors, and helps maintain optimal solar installation performance.
Unique Multimeter Readiness Self-Check
The size and location of utility-scale solar sites can present unique challenges whether they’re logistical, environmental, or testing related. Because of that, you want to have confidence that your meter is fully functional, capturing the right data every time so you don’t have to do the same job twice. The 283 FC features a unique integrated multimeter readiness selfcheck, that ensures your meter is in proper working order before you take your next reading. This quick self-check is an additional readiness test that gives you valuable insight to the status of your meter’s calibration, battery life availability, test lead functionality, and AC/DC voltage measurement functionality so you can be confident that your meter is ready to work when you are.
Logging/Saving
The 283 FC offers convenient logging and saving features that set it apart from other digital multimeters. With a built-in real-time clock, each measurement can be time- and date-stamped for accurate recordkeeping. The multimeter has internal memory to save and log measurements, which can then be easily transferred to Fluke Connect for further analysis. Additionally, you have the flexibility to customize logging durations and intervals, ensuring the logging process matches the specific needs of the system you are testing.
Fluke Connect™ with Fluke Cloud™ Storage
Fluke Connect™ compatibility provides convenient features to enhance your troubleshooting experience. As part of the Fluke Connect family, the 283 FC can transmit measurements to a smartphone or tablet for later, detailed analysis. No need to write down the results. Trend and monitor measurements live on your phone screen and upload those measurements to the cloud. Combine measurement data from multiple Fluke Connect test tools to create and share reports from the job site via email and collaborate in real time with other colleagues with ShareLive™ video calls or email. The table view feature organizes measurements, notes, and images in a clear and efficient manner, making it easier to reference data, identify issues, and generate reports for customers. Fluke Connect™ with Fluke Cloud™ Storage streamlines your workflow and ensures accurate data storage and organization.
Applications
Function | |
AC Volts | Range: 6.000 V Resolution: 0.001 V Accuracy: 1.0% + 3 (45 Hz to 500 Hz) Range: 60.00 V Resolution: 0.01 V Accuracy: 1.0% + 3 (45 Hz to 500 Hz) Range: 600.0 V Resolution: 0.1 V Accuracy: 2.0% + 3 (500 Hz to 1 kHz) Range: 1000 V Resolution: 1 V Accuracy: 2.0% + 3 (500 Hz to 1 kHz) |
DC Volts | Range: 6.000 V Resolution: 0.001 V Accuracy: 0.09% + 3 Range: 60.00 V Resolution: 0.01 V Accuracy: 0.09% + 3 Range: 600.0 V Resolution: 0.1 V Accuracy: 0.15% + 2 Range: 1500 V Resolution: 1 V Accuracy: 0.15% + 2 |
DC mV | Range: 600.0 mV Resolution: 0.1 mV Accuracy: 0.09% + 2 |
AC mV | Range: 600.0 mV Resolution: 0.1 mV Accuracy: 1.0% + 3 (45 Hz to 500 Hz) Range: 600.0 mV Resolution: 0.1 mV Accuracy: 2.0% + 3 (500 Hz to 1 kHz) |
Continuity | Range: 600.0 Ω Resolution: 1 Ω |
Resistance | Range: 600.0 Ω Resolution: 0.1 Ω Accuracy: 0.5% + 4 Range: 6.000 kΩ Resolution: 0.001 kΩ Accuracy: 0.5% + 4 Range: 60.00 kΩ Resolution: 0.01 kΩ Accuracy: 0.5% + 4 Range: 600.0 kΩ Resolution: 0.1 kΩ Accuracy: 0.5% + 4 Range: 6.000 MΩ Resolution: 0.001 MΩ Accuracy: 1.5% + 4 Range: 50.00 MΩ Resolution: 0.01 MΩ Accuracy: 1.5% + 4 |
Capacitance | Range: 1000 nF Resolution: 1 nF Accuracy: 1.2% + 2 Range: 10.00 μF Resolution: 0.01 μF Accuracy: 1.2% + 2 Range: 100.0 μF Resolution: 0.1 μF Accuracy: 10% typical Range: 9999 μF Resolution: 1 μF Accuracy: 10% typical |
Frequency | Range: 99.99 Hz Resolution: 0.01 Hz Accuracy: 0.1% + 2 Range: 999.9 Hz Resolution: 0.1 Hz Accuracy: 0.1% + 2 Range: 9.999 kHz Resolution: 0.001 kHz Accuracy: 0.1% + 2 Range: 99.99 kHz Resolution: 0.01 kHz Accuracy: 0.1% + 2 |
AC VA (45 to 500 Hz) | Range: 360.0 VA Resolution: 0.1 VA Accuracy: 2% + 1.0 VA Range: 3.600 kVA Resolution: 0.001 kVA Accuracy: 2% + 1.0 kVA Range: 36.00 kVA Resolution: 0.01 kVA Accuracy: 2% + 0.15 kVA Range: 60.00 kVA Resolution: 0.1 kVA Accuracy: 2% + 0.15 kVA |
DC VA | Range: 360.0 VA Resolution: 0.1 VA Accuracy: 2% + 1.0 VA Range: 3.600 kVA Resolution: 0.001 kVA Accuracy: 2% + 1.0 kVA Range: 36.00 kVA Resolution: 0.01 kVA Accuracy: 2% + 0.15 kVA Range: 90.00 kVA Resolution: 0.1 kVA Accuracy: 2% + 0.25 kVA |
Environmental Specifications | |
Operating Temperature | -10 to 60°C (14 to 140°F) |
Storage Temperature | -30 to 70°C (-22 to 158°F) |
Humidity (without condensation) | 0 to 90%, 10 to 30°C (50 to 86°F) 0 to 75%, 30 to 40°C (86 to 104°F) 0 to 45%, 40 to 60°C (104 to 140°F) |
Protection | |
Electromagnetic compatibility | IEC 61326-1, IEC 61326-2-2, Portable, Group 1, Class A |
Overvoltage category | CAT III 1500 V, CAT IV 1000 V |
Agency approvals | ETL (AMER and EMEA), CSA (APAC), CE, UK CA |
Drop test | 2 m (6.5') drop test |
Ingress protection | IP52 |
Mechanical and General Specifications | |
Counts | 6000 |
Battery life | > 150 hours typical, without backlight (Alkaline, 3 AA) > 100 hours typical when connected to wireless current clamp (Alkaline, 3 AA) |
Dimensions | 22.5 x 10.5 x 5.7 cm (8.8 x 4.1 x 2.2") |
Weight | 0.7 kg (1.5 lb) |
In the past, motor repair meant dealing with traditional three-phase motor failures that were largely the result of water, dust, grease, failed bearings, misaligned motor shafts, or just plain old age. But motor repair has changed in a big way with the introduction of electronically controlled motors, more commonly referred to as adjustable speed drives (ASDs). These drives present a unique set of measurement problems that can vex the most seasoned pro. Thanks to new technology, now for the first time you can take accurate electrical measurements with a DMM during the installation and maintenance of a drive and diagnose bad components and other conditions that may lead to premature failure.
Technicians use many different methods to troubleshoot an electrical circuit, and a good troubleshooter will always find the problem - eventually. The trick is tracking it down quickly and keeping downtime to a minimum. The most efficient troubleshooting procedure begins at the motor and then works systematically back to the electrical source, looking for the most obvious problems first. A lot of time and money can be wasted replacing perfectly good parts when the problem is simply a loose connection. As you go, take care to take accurate measurements. Nobody takes inaccurate measurements on purpose, but it's easy to do, especially when working in a high-energy, noisy environment like an ASD. Likewise, choosing the right test tools for troubleshooting the drive, the motor, and the connections are of utmost importance. This is especially true when taking voltage, frequency, and current measurements on the output side of the motor drive. But until now, there hasn't been a digital multimeter on the market able to accurately measure ASDs. Incorporates a selectable low pass filter* that allows for accurate drive output measurements that agree with the motor drive controller display indicator. Now, technicians won't have to guess whether the drive is operating correctly and delivering the correct voltage, current, or frequency for a given control setting.
Input side measurements
Any good quality True RMS multimeter can verify proper input power to an ASD. The input voltage readings should be within 1% of one another when measured from phase to phase with no load. A significant unbalance may lead to erratic drive operation and should be corrected when discovered.
Output side measurements
On the flip side, a regular True RMS multimeter can't reliably read the output side of a pulse width modulated (PWM) motor drive, because the ASD applies pulse width modulated nonsinusoidal voltage to the motor terminals. A True RMS DMM reads the heating effect of the non-sinusoidal voltage applied to the motor, while the motor controller's output voltage reading only displays the RMS value of the fundamental component (typically from 30 Hz to 60 Hz). The causes of this discrepancy are bandwidth and shielding. Many of today's True RMS digital multimeters have bandwidths out to 20 kHz or more, causing them to respond not only to the fundamental component, which is what the motor responds to but to all of the high-frequency components generated by the PWM drive. And if the DMM isn't shielded for high-frequency noise, the drive controller's high noise levels make the measurement discrepancies even more extreme. With the bandwidth and shielding issues combined, many True RMS meters display readings as much as 20 to 30% higher than what the drive controller is indicating. The incorporated selectable low pass filter allows troubleshooters to take accurate voltage, current, and frequency measurements on the output side of the drive at either the drive itself or the motor terminals. With the filter selected, the readings for both voltage and frequency (motor speed) should agree with the associated drive control display indications, if available. The low pass filter also allows for accurate current measurements when used with Hall-effect type clamps. All of these measurements are especially helpful when taking measurements at the motor location when the drive's displays are not in view.
Taking safe measurements
Before taking any electrical measurements, be sure you understand how to take them safely. No test instrument is completely safe if used improperly, and many test instruments are not appropriate for testing adjustable speed drives. Also, make sure to use the appropriate personal protective equipment (PPE) for your specific working environment and measurements. If at all possible, never work alone.
Safety ratings for electrical test equipment
ANSI and the International Electrotechnical Commission (IEC) are the primary independent organizations that define safety standards for test equipment manufacturers. The IEC 61010 second edition standard for test equipment safety states two basic parameters: a voltage rating and a measurement category rating. The voltage rating is the maximum continuous working voltage the instrument is capable of measuring. The category ratings depict the measurement environment expected for a given category. Most three-phase ASD installations would be considered a CAT III measurement environment, with power supplied from either 480V or 600V distribution systems. When using a DMM for measurements on these high-energy systems, make sure it's rated at a minimum for CAT III 600V and preferably for CAT IV 600V/CAT III 1000V. The category rating and voltage limit are typically found on the front panel, at the input terminals. Dual-rated CAT IV 600V and CAT III 1000V. Refer to the ABC's of DMM Safety* from Fluke for additional information on category ratings and taking safe measurements.
Now let's put the multimeter to the test. The measurements in the following procedure are designed to be made on a 480 volt 3 phase drive control at the control panel terminal strips. These procedures would also be valid for lower voltage 3 phase drives powered by either single or 3 phase supply voltages. For these tests, the motor is running at 50 Hz.
Input voltage
To measure the ac voltage supply to the input side of the drive at the drive:
Input current
Measuring the input current generally requires a current clamp accessory. In most cases, either the input current exceeds the maximum current measurable by the current function, or it isn't practical to "break the circuit" to take an in-line series current measurement. Regardless of clamp type, insure that all readings are within 10% of each other for proper balance.
Transformer type clamp (i200, 80i-400, 80i-600A)
Hall Effect type (AC/DC) clamp (i410,i-1010)
Figure 1. Output voltage reading without using the low pass filter.
Figure 2. Output voltage reading with low pass filter enabled.
Output voltage
To measure the AC output voltage at either the drive or the motor terminals:
Figure 3. Output frequency (motor speed) without the low pass filter.
Figure 4. Output frequency (motor speed) using the low pass filter.
Motor speed (Output frequency using voltage as a reference)
To determine motor speed, simply take a frequency measurement while using the low pass filter. The measurement can be made between any two of the phase voltage or motor terminals.
Output current
TAs with input current, measuring the output current generally requires a current clamp accessory. Once again, regardless of clamp type, insure that all readings are within 10% of each other for proper balance.
Transformer type clamp (i200, 80i-400, 80i-600A)
Figure 5. Output current reading without using the low pass filter.
Figure 6. Output current reading with low pass filter enabled.
Hall Effect type (AC/DC) clamp (i410,i-1010)
Motor speed (Output frequency using current as a reference)
For motors that pull at least 20 amps of running current, motor speed can be determined by taking a frequency measurement with current clamps. Until now, noise issues have prevented accurate readings using hall effect type clamps. Here's how the low pass filter makes it possible.
Motor speed using a Hall Effect type (AC/DC) clamp (i410,i-1010)
Motor speed using a transformer type clamp (i200, 80i-400, 80i-600A)
DC Bus measurements
A healthy dc bus is a must for a properly operating motor drive. If the bus voltage is incorrect or unstable, the converter diodes or capacitors may be starting to fail. The DC bus voltage should be approximately 1.414 times the phase to phase input voltage. For a 480 volt input, the DC bus should be approximately 679 VDC. The DC bus is typically labeled as DC+, DC- or B+, Bon the drive terminal strip. To measure the DC bus voltage:
Click on a category to view a selection of compatible accessories with the Fluke 283FC True RMS Wireless Multimeter, CAT III 1500 V, CAT IV 1000 V.
Function | |
AC Volts | Range: 6.000 V Resolution: 0.001 V Accuracy: 1.0% + 3 (45 Hz to 500 Hz) Range: 60.00 V Resolution: 0.01 V Accuracy: 1.0% + 3 (45 Hz to 500 Hz) Range: 600.0 V Resolution: 0.1 V Accuracy: 2.0% + 3 (500 Hz to 1 kHz) Range: 1000 V Resolution: 1 V Accuracy: 2.0% + 3 (500 Hz to 1 kHz) |
DC Volts | Range: 6.000 V Resolution: 0.001 V Accuracy: 0.09% + 3 Range: 60.00 V Resolution: 0.01 V Accuracy: 0.09% + 3 Range: 600.0 V Resolution: 0.1 V Accuracy: 0.15% + 2 Range: 1500 V Resolution: 1 V Accuracy: 0.15% + 2 |
DC mV | Range: 600.0 mV Resolution: 0.1 mV Accuracy: 0.09% + 2 |
AC mV | Range: 600.0 mV Resolution: 0.1 mV Accuracy: 1.0% + 3 (45 Hz to 500 Hz) Range: 600.0 mV Resolution: 0.1 mV Accuracy: 2.0% + 3 (500 Hz to 1 kHz) |
Continuity | Range: 600.0 Ω Resolution: 1 Ω |
Resistance | Range: 600.0 Ω Resolution: 0.1 Ω Accuracy: 0.5% + 4 Range: 6.000 kΩ Resolution: 0.001 kΩ Accuracy: 0.5% + 4 Range: 60.00 kΩ Resolution: 0.01 kΩ Accuracy: 0.5% + 4 Range: 600.0 kΩ Resolution: 0.1 kΩ Accuracy: 0.5% + 4 Range: 6.000 MΩ Resolution: 0.001 MΩ Accuracy: 1.5% + 4 Range: 50.00 MΩ Resolution: 0.01 MΩ Accuracy: 1.5% + 4 |
Capacitance | Range: 1000 nF Resolution: 1 nF Accuracy: 1.2% + 2 Range: 10.00 μF Resolution: 0.01 μF Accuracy: 1.2% + 2 Range: 100.0 μF Resolution: 0.1 μF Accuracy: 10% typical Range: 9999 μF Resolution: 1 μF Accuracy: 10% typical |
Frequency | Range: 99.99 Hz Resolution: 0.01 Hz Accuracy: 0.1% + 2 Range: 999.9 Hz Resolution: 0.1 Hz Accuracy: 0.1% + 2 Range: 9.999 kHz Resolution: 0.001 kHz Accuracy: 0.1% + 2 Range: 99.99 kHz Resolution: 0.01 kHz Accuracy: 0.1% + 2 |
AC VA (45 to 500 Hz) | Range: 360.0 VA Resolution: 0.1 VA Accuracy: 2% + 1.0 VA Range: 3.600 kVA Resolution: 0.001 kVA Accuracy: 2% + 1.0 kVA Range: 36.00 kVA Resolution: 0.01 kVA Accuracy: 2% + 0.15 kVA Range: 60.00 kVA Resolution: 0.1 kVA Accuracy: 2% + 0.15 kVA |
DC VA | Range: 360.0 VA Resolution: 0.1 VA Accuracy: 2% + 1.0 VA Range: 3.600 kVA Resolution: 0.001 kVA Accuracy: 2% + 1.0 kVA Range: 36.00 kVA Resolution: 0.01 kVA Accuracy: 2% + 0.15 kVA Range: 90.00 kVA Resolution: 0.1 kVA Accuracy: 2% + 0.25 kVA |
Environmental Specifications | |
Operating Temperature | -10 to 60°C (14 to 140°F) |
Storage Temperature | -30 to 70°C (-22 to 158°F) |
Humidity (without condensation) | 0 to 90%, 10 to 30°C (50 to 86°F) 0 to 75%, 30 to 40°C (86 to 104°F) 0 to 45%, 40 to 60°C (104 to 140°F) |
Protection | |
Electromagnetic compatibility | IEC 61326-1, IEC 61326-2-2, Portable, Group 1, Class A |
Overvoltage category | CAT III 1500 V, CAT IV 1000 V |
Agency approvals | ETL (AMER and EMEA), CSA (APAC), CE, UK CA |
Drop test | 2 m (6.5') drop test |
Ingress protection | IP52 |
Mechanical and General Specifications | |
Counts | 6000 |
Battery life | > 150 hours typical, without backlight (Alkaline, 3 AA) > 100 hours typical when connected to wireless current clamp (Alkaline, 3 AA) |
Dimensions | 22.5 x 10.5 x 5.7 cm (8.8 x 4.1 x 2.2") |
Weight | 0.7 kg (1.5 lb) |
In the past, motor repair meant dealing with traditional three-phase motor failures that were largely the result of water, dust, grease, failed bearings, misaligned motor shafts, or just plain old age. But motor repair has changed in a big way with the introduction of electronically controlled motors, more commonly referred to as adjustable speed drives (ASDs). These drives present a unique set of measurement problems that can vex the most seasoned pro. Thanks to new technology, now for the first time you can take accurate electrical measurements with a DMM during the installation and maintenance of a drive and diagnose bad components and other conditions that may lead to premature failure.
Technicians use many different methods to troubleshoot an electrical circuit, and a good troubleshooter will always find the problem - eventually. The trick is tracking it down quickly and keeping downtime to a minimum. The most efficient troubleshooting procedure begins at the motor and then works systematically back to the electrical source, looking for the most obvious problems first. A lot of time and money can be wasted replacing perfectly good parts when the problem is simply a loose connection. As you go, take care to take accurate measurements. Nobody takes inaccurate measurements on purpose, but it's easy to do, especially when working in a high-energy, noisy environment like an ASD. Likewise, choosing the right test tools for troubleshooting the drive, the motor, and the connections are of utmost importance. This is especially true when taking voltage, frequency, and current measurements on the output side of the motor drive. But until now, there hasn't been a digital multimeter on the market able to accurately measure ASDs. Incorporates a selectable low pass filter* that allows for accurate drive output measurements that agree with the motor drive controller display indicator. Now, technicians won't have to guess whether the drive is operating correctly and delivering the correct voltage, current, or frequency for a given control setting.
Input side measurements
Any good quality True RMS multimeter can verify proper input power to an ASD. The input voltage readings should be within 1% of one another when measured from phase to phase with no load. A significant unbalance may lead to erratic drive operation and should be corrected when discovered.
Output side measurements
On the flip side, a regular True RMS multimeter can't reliably read the output side of a pulse width modulated (PWM) motor drive, because the ASD applies pulse width modulated nonsinusoidal voltage to the motor terminals. A True RMS DMM reads the heating effect of the non-sinusoidal voltage applied to the motor, while the motor controller's output voltage reading only displays the RMS value of the fundamental component (typically from 30 Hz to 60 Hz). The causes of this discrepancy are bandwidth and shielding. Many of today's True RMS digital multimeters have bandwidths out to 20 kHz or more, causing them to respond not only to the fundamental component, which is what the motor responds to but to all of the high-frequency components generated by the PWM drive. And if the DMM isn't shielded for high-frequency noise, the drive controller's high noise levels make the measurement discrepancies even more extreme. With the bandwidth and shielding issues combined, many True RMS meters display readings as much as 20 to 30% higher than what the drive controller is indicating. The incorporated selectable low pass filter allows troubleshooters to take accurate voltage, current, and frequency measurements on the output side of the drive at either the drive itself or the motor terminals. With the filter selected, the readings for both voltage and frequency (motor speed) should agree with the associated drive control display indications, if available. The low pass filter also allows for accurate current measurements when used with Hall-effect type clamps. All of these measurements are especially helpful when taking measurements at the motor location when the drive's displays are not in view.
Taking safe measurements
Before taking any electrical measurements, be sure you understand how to take them safely. No test instrument is completely safe if used improperly, and many test instruments are not appropriate for testing adjustable speed drives. Also, make sure to use the appropriate personal protective equipment (PPE) for your specific working environment and measurements. If at all possible, never work alone.
Safety ratings for electrical test equipment
ANSI and the International Electrotechnical Commission (IEC) are the primary independent organizations that define safety standards for test equipment manufacturers. The IEC 61010 second edition standard for test equipment safety states two basic parameters: a voltage rating and a measurement category rating. The voltage rating is the maximum continuous working voltage the instrument is capable of measuring. The category ratings depict the measurement environment expected for a given category. Most three-phase ASD installations would be considered a CAT III measurement environment, with power supplied from either 480V or 600V distribution systems. When using a DMM for measurements on these high-energy systems, make sure it's rated at a minimum for CAT III 600V and preferably for CAT IV 600V/CAT III 1000V. The category rating and voltage limit are typically found on the front panel, at the input terminals. Dual-rated CAT IV 600V and CAT III 1000V. Refer to the ABC's of DMM Safety* from Fluke for additional information on category ratings and taking safe measurements.
Now let's put the multimeter to the test. The measurements in the following procedure are designed to be made on a 480 volt 3 phase drive control at the control panel terminal strips. These procedures would also be valid for lower voltage 3 phase drives powered by either single or 3 phase supply voltages. For these tests, the motor is running at 50 Hz.
Input voltage
To measure the ac voltage supply to the input side of the drive at the drive:
Input current
Measuring the input current generally requires a current clamp accessory. In most cases, either the input current exceeds the maximum current measurable by the current function, or it isn't practical to "break the circuit" to take an in-line series current measurement. Regardless of clamp type, insure that all readings are within 10% of each other for proper balance.
Transformer type clamp (i200, 80i-400, 80i-600A)
Hall Effect type (AC/DC) clamp (i410,i-1010)
Figure 1. Output voltage reading without using the low pass filter.
Figure 2. Output voltage reading with low pass filter enabled.
Output voltage
To measure the AC output voltage at either the drive or the motor terminals:
Figure 3. Output frequency (motor speed) without the low pass filter.
Figure 4. Output frequency (motor speed) using the low pass filter.
Motor speed (Output frequency using voltage as a reference)
To determine motor speed, simply take a frequency measurement while using the low pass filter. The measurement can be made between any two of the phase voltage or motor terminals.
Output current
TAs with input current, measuring the output current generally requires a current clamp accessory. Once again, regardless of clamp type, insure that all readings are within 10% of each other for proper balance.
Transformer type clamp (i200, 80i-400, 80i-600A)
Figure 5. Output current reading without using the low pass filter.
Figure 6. Output current reading with low pass filter enabled.
Hall Effect type (AC/DC) clamp (i410,i-1010)
Motor speed (Output frequency using current as a reference)
For motors that pull at least 20 amps of running current, motor speed can be determined by taking a frequency measurement with current clamps. Until now, noise issues have prevented accurate readings using hall effect type clamps. Here's how the low pass filter makes it possible.
Motor speed using a Hall Effect type (AC/DC) clamp (i410,i-1010)
Motor speed using a transformer type clamp (i200, 80i-400, 80i-600A)
DC Bus measurements
A healthy dc bus is a must for a properly operating motor drive. If the bus voltage is incorrect or unstable, the converter diodes or capacitors may be starting to fail. The DC bus voltage should be approximately 1.414 times the phase to phase input voltage. For a 480 volt input, the DC bus should be approximately 679 VDC. The DC bus is typically labeled as DC+, DC- or B+, Bon the drive terminal strip. To measure the DC bus voltage: